INSTALLATION AND OPERATOR’S MANUAL
SL375 THRU SL7175
OIL FIRED CAST IRON BOILERS
Keep these instructions with the boiler at all times for
future reference
B
OYERTOWN FURNACE CO.
PO Box 100
B
OYERTOWN, PA 19512
1-610-369-1450
www.boyertownfurnace.com
1-10-06
Vista de pagina 0
1 2 3 4 5 6 ... 31 32

Indice de contenidos

Pagina 1 - SL375 THRU SL7175

INSTALLATION AND OPERATOR’S MANUAL SL375 THRU SL7175 OIL FIRED CAST IRON BOILERS Keep these instructions with the boiler at all times fo

Pagina 2

10 VENTING Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe

Pagina 3 - Table of Contents

11 Evidence of potential or existing chimney damage should be determined by visual inspection of the chimney and liner. Exterior indicators such as

Pagina 4 - Ratings and Data

12 With the burner operating, use a draft gauge to adjust the regulator to the proper setting (see instructions enclosed with draft gauge to adjust t

Pagina 5 - Warning…

13 3. COMBINATION AIR INTAKE/VENT SYSTEM The vent system consists of 10, 15, or 20 foot lengths of 5” single wall flexible sta

Pagina 6 - Boiler Assembly

14 The purpose of the damper is to act as a vacuum breaker in the event of a blockage in the air intake. NOTE: The balance weight of the vacuum rel

Pagina 7 - Boiler Trim Piping

15DIRECT VENT OIL BURNERS Riello Burners All Riello direct vent burners are shipped with the nozzle for the SLD375 installed. A separate nozzle is

Pagina 8 - Jacket installation

16 Oil Tank and Piping Oil tanks and piping should be installed in accordance with the National Board of Fire Underwriters and local codes. Connect

Pagina 11

19Swing Door Opening the Door 1. Turn off power to boiler. 2. Allow boiler to cool down. 3. Unplug the burner power cable at factory-supplied bur

Pagina 12 -

2 Be Aware of Hazard Definitions Denotes presence of a hazard which, if ignored, will result in severe personal injury, death or property damage Dang

Pagina 13

20 Carlin 90200A Temperature Control 1. The Carlin 90200A temperature control functions as a high limit only. Start-Up Warning…Use only … No. 2 f

Pagina 14

212. Direct vented – Take a draft reading from the inspection port of the boiler. This over-fire reading will be a positive pressure. Approximate

Pagina 15 - Burner Installation

22 1. High limit control - Remove the temperature control cover as needed and note temperature setting. With the burner running reduce the high lim

Pagina 16 - Electrical Wiring

232. Clean nozzle assembly and all air handling parts. 3. Check spacing and condition of ignition electrodes. Clean and replace as required. 4. N

Pagina 17

24 Trouble Shooting Guide Burner Will Not Start Thermostat SetAbove RoomTemperatureHigh Limit Set onAquastat to 180Deg. Min.110 Volts betweenL1 and

Pagina 18

25Burner Goes Off On Safety Oil Tank FullBleed Oil LinesOil Flows FreelyAir in Oil LinesPump Pressureto Burner Spec.SparkEstablishedNozzle CleanMatc

Pagina 19 - Operation

26 Item Qty. Description SL375 SL4100 SL5215 SL6150 SL6175 1 1 Riello F-5 Oil Burner 541151 541147 541148 541149 N/A 1

Pagina 20 - Burner Adjustments

27Solaia Residential Cast Iron Boiler Warranty First Year Limited Warranty for Solaia Residential Cast Iron Water Boilers Boyertown Furnace warrants

Pagina 21 - Preliminary Burner Settings

28 Installation and Service Check List Boiler Model: _______________________ Serial No.: ____________________ Install

Pagina 22 - Maintenance

29 -----------------Cut and Return This Form or register online at www.boyertownfurnace.com----------------- W

Pagina 23 - Vent System

3Table of Contents Ratings and Data………………………………………………………………………4 Clearances……………………………………………………………………...5 Ventilation and Combustion A

Pagina 27

4 Ratings and Data Boiler Model No. SL375 SLD375 SL4100 SLD4100 SL5125 SLD5125 SL6150 SL7175 Firing Rate - #2 Fuel 0.75 0.75 1.00 1.

Pagina 28

5Installation Clearances Boilers in rooms shall be installed with the clearances from combustible materials not less than indic

Pagina 29 - Warranty Registration

6 hundred (100) square inches. These openings must freely communicate with the interior areas having adequate infiltration from the outside. When

Pagina 30

7the crated boiler to the carrier in good condition. ANY CLAIMS FOR DAMAGE OR SHORTAGE IN SHIPMENT MUST BE FILED IMMEDIATELY against the carrier by

Pagina 31

8 Jacket installation 1. Open Cabinet Parts Box Check for damages. Damage claims must be filed immediately with carrier. 2. Install the (4) 3/4” O

Pagina 32

9 System Piping Important… INSTALLATION MUST BE PERFORMED BY TECHNICALLY QUALIFIED SERVICEMEN SOLAIA BOILERS HAVE A MAXIMUM OPERATING PRESSURE OF