Speci cations
Input ring range 300 to 1200 MBh
Fuel Natural gas - 0.6 speci c gravity typical
Gas train Standard: UL listed/CSD-1 Con guration
Options: IRI and FM
Manifold pressure 1.0 to 4.6 inches W.C. typical
Firing mode On/Off or On/Off with Low Fire Start
Flame safeguard RM7895A Standard (Options available)
Flame detection Standard: Flame rod recti cation
Optional: Ultraviolet scanner
Air proving switch Standard
Gas pressure
switches
Standard high and low
Ignition Direct spark main ame
Motor Standard: 1/3 HP; 3450 RPM; 120 volt/60 hz,
single phase
Optional motor: 50 or 60 hz (see notice for 50
hz), 240 volt single phase
Weight 55 lbs.
Features
S - Standard O - Optional N/A - Not Available
On/Off with Low Fire Start S
Propane Restrictor O
Linkageless Low/High/Low or Low/High/Off N/A
Modulation with Pressure/Temperature Modulating Controller N/A
Right or Left Side Gas Train Connection S
Air Pressure Switch S
Low Gas Pressure Switch S
High Gas Pressure Switch S
Main Shutoff Cock, Leak Test Cock, Test Connections, and Test Cocks S
Direct Spark Ignition of Main Flame S
Flame Safeguard with Flame Rod O
Flame Safeguard with UV Sensor S
Customized Electrical Cabinet O
UL/CUL - CSD1 - Swiss Re S
FM O
IRI (old standard) O
Power On - Fuel On, Indicator Light O
11.7
6.0
8.1
4.4
4.6
25.5
6.8
8.2
9.9-11.0
Overall Dimensions
Gas Gun Assembly
BECKETT
CG10
COMMERCIAL GAS BURNER
Gas Train Assembly (Typical Gas Train, other con gurations are available)
LGPS
TC TC HGPS
MSC
U SSOV1 2PRSSOV MLTC U TP
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Gas Gun Assembly

www.beckettcorp.com R.W. Beckett Corporation ● Elyria, OhioSpecifi cationsInput fi ring range 300 to 1200 MBhFuel Natural gas - 0.6 specifi c gravity t

Pagina 2 - Chamber Dimensions (inches)

Typical Wiring (Honeywell RM7897A - for reference only) Minimum CombustionChamber Dimensions (inches)Input Firing Rate in MBH‘L’ (Length)‘W’ (Width)‘H