Potential for Fire, Smoke and Asphyxiation HazardsTo the Homeowner or Equipment Owner:Please read and carefully follow all instructions provided in th
10Burner fuel fl owOne-pipe systems – See Figure 10 for the fuel fl ow path.Oil supply connects to one of the fuel unit inlet ports.Two-pipe systems – S
11CF375 Burner ManualFigure 12 - 7505 Control Section: Wire the BurnerFire or Explosion HazardCan cause severe injury, death, or property damage.The c
12Ignition Carryover: Once fl ame is established, the igniter remains on for 10 additional seconds to ensure fl ame stability. Run: The fl ame is sustai
13CF375 Burner ManualFigure 13a. – Interrupted ignition, valve-on delay only (no motor-off delay)Figure 13b. – Interrupted ignition, valve-on delay an
14STANDBY. The burner is idle, waiting for a call for heat. When a call for heat is initiated, there is a 3-10 second delay while the control performs
15CF375 Burner ManualPrepare the Burner for Start-upStart-up checklistVerify the following before attempting to start burner.Combustion air supply and
16Table 5 - Initial indicator adjustment plate settings (head position)Approximate adjusting plate settingFiring rate, gph0 1.651 1.753 2.
17CF375 Burner Manual- Priming the Pump For 7505 Control:Initiate a call for heat.After the burner starts, press and hold the reset button for 15 seco
18Section: Maintenance and ServiceStep 4: Recheck smoke level. It should be Zero.This procedure provides a margin of reserve air to accommodate varia
19CF375 Burner ManualItem Name/Description Part Number1 Air Tube See Figure 32 Spline Nut 36663 Adjusting plate assembly 57214 Blocking Oil Solenoid V
2To the Owner:Thank you for purchasing a Beckett burner for use with your heating appliance. Please pay attention to the Safety Warnings contained wi
USA: P.O. Box 1289 ● Elyria, Ohio 44036Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road ● Guelph, Ontario N1G 3X7www.beckettcorp.comPart Nu
3CF375 Burner ManualAgency approvalsUL listed to comply with ANSI/UL296 and certifi ed to CSA B140.0.Accepted by N.Y.C. M.E.A.Other approvals may be av
4Owner’s Responsibility: Professional Installer/Service Agency Responsibility:Pre-Installation ChecklistCombustion air supply31. For appliance/burner
5CF375 Burner ManualFuel supply Nozzle pressureSection: Pre-Installation ChecklistThe fuel supply piping and tank must provide #1 or #2 fuel oil at pr
6Inspect Chimney or Direct Vent SystemTable 1 - Nozzle CapacitiesRated gph @ 100 psigPressure - pounds per square inch125 140 1501.35 1.51 1.60 1.651
7CF375 Burner ManualVerify fi ring rateRefer to appliance manufacturer’s instructions (if available) for fi ring rate and nozzle selection. Otherwise, t
8Mount the BurnerMount fl ange(s) on air tubeThis section does not apply to burners with welded fl anges.Do not install air tube on burner.For non-press
9CF375 Burner ManualFigure 8 - Adjusting plate assy.Figure 7 - Nozzle line assembly in burner1-1/2”Legend (Figure 8)cBottom acorn nutdFastenereIndicat