Professional Installation and Service Required
Incorrect installation and mishandling of startup could lead to equipment malfunction
and result in asphyxiation, explosion, or re.
y This Gas Burner Supplement shall be used in conjunction with the Beckett 6104 BCG50 Installation Manual.
y This burner shall only be installed and prepared for startup by a qualied service technician who is trained and
experienced in commercial gas burner system installation and operation.
y Carefully follow the wiring diagrams, control instruction sheets, ame safeguard sequence of operation, test procedures
and all appliance manufacturer’s directions that pertain to this installation.
y Perform all wiring in accordance with the National Electric Code ANSI/NFPA 70, Canada CSA C22.1 and all authorities
having jurisdiction.
y If any of these items are not clear or are unavailable, call Beckett at 1-800-645-2876 for assistance.
Gas Burner Manual Supplement
CG15 / CG25 / CG50 Optional Modulation Control Systems
COMMERCIAL PRODUCTS
I. Introduction
The CG15, CG25, and CG50 gas burners are available
in three optional congurations that can be controlled
by the three most popular modulation control signals:
135 Ohm, 4 – 20 mA, or 2 – 10 VDC. All three of these
options use the Siemens SQM40 actuator for damper
control. The SQM40 accepts any of those signals, so the
difference between burners using any of those control
signals is internal wiring of the burner, the control signal
connections you make, and trim adjustments. When
operating with any of these signals, the burner’s ring
rate responds in a direct proportional control manner,
making them well suited for use with lead/lag or building
automation system controls. The standard burner
conguration for these modulation systems is with the
junction box (shown in Figure 1), but a panel enclosure
is optionally available.
Operator controls are the
same for all 3 signal types.
Siemens SQM40 actuator
Figure 1
Vista de pagina 0
1 2 3 4

Indice de contenidos

Pagina 1 - Gas Burner Manual Supplement

1Professional Installation and Service RequiredIncorrect installation and mishandling of startup could lead to equipment malfunction and result in asp

Pagina 2 - II. Wiring

2III. Damper Motor ComponentsThe damper motor positions for high  re and for low  re are set by adjustment of individual cams in a cam stack (Shown

Pagina 3 - IV. Adjustment Instructions

3CG15 / CG25 / CG50 Optional Modulation Control SystemsFigure 5Maximum position potentiometerCam disengaging pinMinimum position potentiometerIV. Adju

Pagina 4 - USA: P.O. Box 1289

4Part Number 61855 R01, Printed in the U.S.A. 11/13COMMERCIAL PRODUCTSUSA: P.O. Box 1289 ● Elyria, Ohio 44036Canada: R.W. Beckett Canada, Ltd. ● U

Comentarios a estos manuales

Sin comentarios