Beckett 61759 Gas Igniter Manual de usuario

Busca en linea o descarga Manual de usuario para Equipo Beckett 61759 Gas Igniter. Beckett 61759 Gas Igniter User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 2
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
INSTALLATION INSTRUCTIONS
ELECTRONIC GAS IGNITER
240 VAC
Electrical Shock Hazard
Failure to disconnect all power sources
could result in severe personal injury or
death.
Disconnect all electrical power to the burner before servicing.
There could be more than one disconnect switch in the supply
circuit.
Installation and service must only be performed by a quali ed
service technician.
Perform all wiring in compliance with the National Electric Code
ANSI/NFPA 70 (Canada CSA C22.1).
Connect burner housing and circuit to earth ground.
y
y
y
y
APPLICATION INFORMATION:
This igniter is secondary one-end ground and designed for use with 240 VAC Beckett gas burners.
It is rated for continuous duty and can be used with intermittent, or interrupted ignition primary controls.
The Beckett gas igniter is designed to mount in the same manner as standard ignition transformers and igniters.
This igniter can be adapted to multiple base plates to accommodate Beckett residential and commercial burners.
CAUTION! Do not use this igniter beyond its design speci cations. Improper operation and igniter failure may result.
SPECIFICATIONS:
Input Voltage: 168-264 VAC, 50/60 Hz
Output Voltage: 19 kV peak
Output Current: 25 mA RMS
Input Current: 0.3A
Secondary One-end Ground
Ambient Operating Temperature: -40 to +150° F
Storage Temperature: -40 to +150° F
Moisture: 5 to 95% Relative Humidity, Condensing
Table 1 - Complete Igniter Base Plate Assemblies
Part No. Burner Models
5199704U CG10 & CG10A
5199705U CG15, CG25, & CG50
Note: Use #6 x 7/16” screws when using the bottom mounting
holes. Use #10 thread forming paint scraping screws, if using
the two top mounting holes for 5199704. For 5199705, use
1/4” machine screws, placing (1) 1/4” lockwasher between
screwhead and baseplate to ensure ground for 5199705.
Tighten all screws securely.
Install base plate gaskets for Beckett CG10, CG15, CG25 and
CG50 burners.
Use of top mounting screws is possible for Beckett CG10
through CG50 burners.
Mount the assembled unit to the burner using the screws
supplied.
Use “paint scraping” screws for all burners (2 at the hinge and
at least 2 for non-hinged base plates). Tighten these screws
securely to provide effective grounding to burner housing.
Verify the burner is properly grounded.
Carefully route the igniter input leads to prevent them from
being pinched during closing.
Wire white to neutral and blue to primary control ignition
lead. Refer to the burner or appliance manufacturer’s wiring
diagram.
Verify the igniter secondary output terminal lead is correctly
arranged to make good electrical contact with the gas burner
electrode.
Verify the ignition electrode gap and orientation are set to the
manufacturer’s speci cations.
Close the igniter. Install and securely tighten the two front
base plate retaining screws (4 screws if no hinge).
Reconnect electric power to the burner circuit.
Verify with instruments that the burner is adjusted to the
manufacturer’s recommended settings
Cycle the burner several times to verify prompt and smooth
ignition before leaving.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
Installation Instructions (If base plate is already
installed, skip to step number 8):
Locate the igniter blue “hot” and the white “neutral” input leads.
Install the 32411 igniter gasket, if required, and route the leads
through the appropriate base plate lead exit hole. Make sure
these leads are not being crushed.
Mount the igniter ush to base plate with the mounting screws
supplied.
1.
2.
3.
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - 240 VAC

INSTALLATION INSTRUCTIONSELECTRONIC GAS IGNITER ● 240 VACElectrical Shock HazardFailure to disconnect all power sources could result in severe persona

Pagina 2 - BECKETT CORPORATION

R.W. BECKETT CORPORATIONP.O. Box 1289, Elyria, Ohio 44036R.W. BECKETT CANADA, LTD430 Laird, Unit 3, Guelph, Ontario, N1G 3X7Part No. 61759 R02, Print

Comentarios a estos manuales

Sin comentarios